If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Diplodocs provides you a fast and easy access to the user manual SIEMENS MICROMASTER 440. We hope that this SIEMENS MICROMASTER 440 user guide will be useful to you.
You may also download the following manuals related to this product:
SIEMENS MICROMASTER 440 (1155 ko)
Manual abstract: user guide SIEMENS MICROMASTER 440
Detailed instructions for use are in the User's Guide.
[. . . ] MICROMASTER 440
Operating instructions Issue A1
User Documentation
MICROMASTER 440 DOCUMENTATION
Getting Started Guide Is for quick commissioning with SDP and BOP.
Operating Instructions Gives information about features of the MM440, Installation, Commissioning, Control modes, System Parameter structure, Troubleshooting, Specifications and available options of the MM440.
Parameter List The Parameter List contains the description of all Parameters structured in functional order and a detailed description. The Parameter list also includes a series of function plans.
Reference Manual The Reference Manual gives detailed information about engineering communication troubleshooting and maintenance.
Catalogues In the catalogue you will find all the necessary information to select an appropriate inverter, as well as filters, chokes, operator panels and communication options.
Overview
1 2 3 4 5 6 7 8 9
A B C D E F G H I J K L
Installation
Commissioning
MICROMASTER 440
Using the MICROMASTER 440 System Parameters
Operating instructions User Documentation
Troubleshooting
MICROMASTER 440 Specifications Available options
Electro-Magnetic Compatibility Appendices
Valid for Converter Type MICROMASTER 440 Control Version 04. 2001
Index Issue A1
IMPORTANT NOTICE
Not all inverters currently have UL approval. UL listing can be determined by examining the inverter's Rating Label.
For UL listed products the following UL mark is used:
Further information can be obtained from Internet website: http://www. siemens. de/micromaster Approved Siemens Quality for Software and Training is to DIN ISO 9001, Reg. 2160-01 The reproduction, transmission or use of this document, or its contents is not permitted unless authorized in writing. [. . . ] The value selected in P0005 (If P0005 is set to show any of the above (3, 4, or 5) then this will not be shown again). Jump Function From any parameter (rXXXX or PXXXX) a short press of the Fn button will immediately jump to r0000, you can then change another parameter, if required. Upon returning to r0000, pressing the Fn button will return you to your starting point. parameters Increase value Decrease value
Figure 3-5
Functions
Pressing this button increases the displayed value.
Pressing this button decreases the displayed value.
Buttons on the Basic Operator Panel
MICROMASTER 440
40
Operating instructions 6SE6400-5CA00-0BP0
International English
3 Commissioning
Changing parameters with the BOP
The following descriptions show how to change the parameters; use this description as a guide for setting any parameters using the `BOP'. Changing P0004 parameter filter function
Step
1 Press to access parameters
Result on display
2
Press
until P0004 is displayed
3
Press
to access the parameter value level
4
Press
or
to the required value
5 6
Press
to confirm and store the value
Only the motor parameters are visible to the user.
Changing P1082 an indexed parameter setting maximum motor frequency
Step
1 Press to access parameters
Result on display
2
Press
until P1082 is displayed
3
Press
to access the parameter value level
4
Press
to display current set value
5
Press
or
to the required value
6
Press
to confirm and store the value
7
Press
until r0000 is displayed
8
Press to return the display to the standard drive display (as defined by the customer)
Figure 3-6
Changing parameters via the BOP
MICROMASTER 440 Operating instructions 6SE6400-5CA00-0BP0
41
3 Commissioning
International English
Note - Busy Message In some cases - when changing parameter values - the display on the BOP shows . This means the inverter is busy with tasks of higher priority.
Changing single digits in Parameter values
For changing the parameter value rapidly, the single digits of the display can be changed by performing the following actions: Ensure you are in the parameter value changing level (see "Changing parameters with BOP"). Press the to leave the parameter value changing level.
Note The function button may also be used to acknowledge a fault condition
Motor data for parameterization
P0308 P0310
P0304 3_Mot IEC 56 IM B3 230/400V 0. 61 0. 35 A 0. 12kW 2800 / min P0305 P0311 P0307 Nr. ED510 3053 IP54 Rot KL 16 60 Hz 440V Y 0. 34A 0. 14 kW Cos j0. 81 3310 /min S. F. -- 1. 15 12. 022 I. CI. F
50 Hz Cos j0. 81 65% P0309
Figure 3-7
Typical Motor Rating Plate Example
MICROMASTER 440
42
Operating instructions 6SE6400-5CA00-0BP0
International English
3 Commissioning
Note P0308 & P0309 are only visible if P0003 2. Only one of the parameters is shown depending on the settings of P0100. in the above example delta terminal connection is for 230 V.
External motor thermal overload protection
When operated below rated speed, the cooling effect of fans fitted to the motor shaft is reduced. Consequentially, most motors require de-rating for continuous operation at low frequencies. To ensure that the motors are protected against overheating under these conditions, a PTC temperature sensor must be fitted to the motor and connected to the inverter control terminals and P0601 enabled.
3. 2. 4. 3
Commissioning with the Advanced Operator Panel (AOP)
The Advanced Operator Panel (AOP) is available as an option. Its advanced features include the following: Multilingual clear text display Upload/download of multiple parameter sets Multidrop capability to drive up to 30 inverters Please refer to the AOP Manual for details or contact your local Siemens sales office for assistance.
3. 3
General operation
For a full description of standard and extended parameters, please refer to the Parameter List. The inverter does not have a main power switch and is live when the mains supply is connected. It waits, with the output disabled, until the RUN button is pressed or for the presence of a digital ON signal at terminal 5 (rotate right). If a BOP or an AOP is fitted and the output frequency is selected to be displayed (P0005 = 21) the corresponding setpoint is displayed approximately every 1. 0 seconds while the inverter is stopped. The inverter is programmed at the factory for standard applications on Siemens four-pole standard motors that have the same power rating as the inverters. When using other motors it is necessary to enter the specifications from the motor's rating plate. You must set P0010 back to 0 in order to initiate a run.
MICROMASTER 440 Operating instructions 6SE6400-5CA00-0BP0
43
3 Commissioning
International English
MICROMASTER 440
44
Operating instructions 6SE6400-5CA00-0BP0
International English
4 Using the MICROMASTER 440
4
Using the MICROMASTER 440
An explanation of the various methods of controlling the inverter An outline of some of the more commonly used parameters of the MICROMASTER 440 which will allow the user to configure the inverter for a number of applications. A brief summary of all the inverter's control modes and an introduction to the inverter's fault and warning reporting capability. More detailed information can be found in the Parameter List and the Reference manual associated with the MICROMASTER 440.
This Chapter contains:
4. 1 4. 2 4. 3 4. 4 4. 5
Frequency Setpoint (P1000) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [. . . ] This file must be approved by a `Competent Body' appointed by the appropriate European government organization. This approach allows the use of standards that are still in preparation.
9. 1. 3
EC Type Examination Certificate
This approach is only applicable to radio communication transmitting apparatus. All MICROMASTER units are certified for compliance with the EMC directive, when installed in accordance with the recommendations in Section 2.
MICROMASTER 440
92
Operating instructions 6SE6400-5CA00-0BP0
International English
9 Electro-Magnetic Compatibility (EMC)
9. 1. 4
EMC Directive Compliance with Imminent Harmonics Regulations
From 1st January 2001 all electrical apparatus covered by the EMC Directive will have to comply with EN 61000-3-2 "Limits for harmonic current emissions (equipment input <= 16A per phase)". All Siemens variable speed drives of the MICROMASTER, MIDIMASTER, MICROMASTER Eco and COMBIMASTER ranges, which are classified as "Professional Equipment" within the terms of the standard, fulfill the requirements of the standard. [. . . ]