Detailed instructions for use are in the User's Guide.
[. . . ] GEM-C Combination Burglary/Access/ Fire System; UL 864, 9th Edition Isolated commercial Burg. /Access and Fire buses and option for separate burg/access battery backups-- easy calcs. , ideal for AHJs. Uses familiar Quickloader Up/downloading and Gemini style keypads in burglary or fire models.
More zones 255, 128 or 32 points More power 7 amps More NAC's Up to 4 on board Built in strobe/horn synch More standby power 32 Amp hour battery capacity Regulated 24V output
Regulated Auxiliary Power Supplies Commercial burglary or fire, 12V regulated 2A models (fire shown); or 1. 75A version with plug-in transformer. [. . . ] Report is generated in 3 ways- either remotely (uploaded) or locally through notebook PC or use optional onsite printer. · Isolated backup battery circuits for Burglary and Fire for EZ backup calculation and AHJ compliance; allows dealer to accommodate separate backup times for burg and fire. This allows burg system to drop out after burg battery depletion, while fire system is maintained and extremely stable for extended period. · Full line of UL Commercial Devices for more flexibility & labor-savings Example, Use Gemini Commercial Wireless 2-input module (GEMCWL-WD2) to convert any UL listed device into a UL wireless device, ideal for sprinkler supervisories or for use with pull stations (mounts on top of wall/conduit or in deep sngle-gang box (plastic). Firewolf Fire-Only 24V Intelligent Addressable Fire Configuration, NFPA72 · Main Control board - supports (1) Addressable Fire SLC controller · Fire 4-wire bus for keypads and conventional devices · Power Supply 7A and 4A · RS-232 Printer Module · Fire Keypad with Gemini-style Menu-functionality · Dual Phone Line built in; Synch module built in (System Sensor & Wheelock protocols) NAC Extender - Powerful flexibility · Nearly 7Amps power · 4 onboard NACs with up to 2A ea. , expandable for up to 24 per system · Up to 16Ah total battery capacity · Regulated 24V Aux. power · Distributes synched bell and strobe outputs with built-in module · Monitors AC, battery trouble, tamper and ground fault on Napco bus -or- provides universal FACP support. Gemini-C Intrusion-Only Configuration, Commercial Conventional/ Addressable 255-Zone Burglary System · Supports full line of new GEMC Commercial-rated addressable conventional, or wireless devices simultaneously · 8 to 255 fully-configurable zones, with up to 8 partitions · Familiar Napco Quickloader up/downloading and keypad operation · 32Ah, max. battery capacity Agencies NFPA 72, UL Commercial Fire, UL864 9th Ed. , SIA CP01, UL985. UL household & commercial burg. : UL1610, UL609, UL365, UL1023 (CSFM, FM, MEA listings pending. )
GEMC & FIREWOLF SYSTEM COMPONENTS
GEMINI C-SERIES COMMERCIAL COMBINATION CONTROL PANEL
Platform supports commercial analog, addressable, wireless or conventional fire or burglary devices.
B U R G L AR Y B U S D E V I C E S
GEMC-BM or GEMC-BM/PS
4 OR 7 AMP MAIN POWER SUPPLY (GEMC-PS24V7A-R or GEMC-PS24V4A-R)
FIRE BUS DEVICES
GEMC-F8ZCPIM 8 Fire Zone Expander
GEMC-EZM8
ACCESS CONTROL DEVI CES
GEMC-RS232
BURGLARY MODULE
GEMC-EZM8
SERIAL OUTPUT CONVERTER
2-WIRE 2-WIRE 2-WIRE 2-WIRE 2-WIRE 2-WIRE 2-WIRE
GEM-ACM1D
GEMC-RECV
GEMINI C-SERIES MOTHERBOARD
8 ZONE CONVENTIONAL ZONE EXPANSION MODULE
GEMC-RECV
WIRELESS RECEIVER
WIRELESS RECEIVER
8 ZONE CONVENTIONAL ZONE EXPANSION MODULE
(4, MAX. )
2-WIRE
ACCESS CONTROL MODULE (4, MAX. )
+ + +
SMOKE 2-WIRE
(4, MAX. )
(31, MAX. )
GEMC-OUT8
S
+
SMOKE 2-WIRE
+ +
S
SMOKE 2-WIRE
+
S S
SMOKE
+
S S
+ +
S
SMOKE 2-WIRE
+ +
S
SMOKE 2-WIRE
+ +
S
SMOKE 2-WIRE
+ +
S
SMOKE 2-WIRE
SMOKE 2-WIRE
MUST BE ALL WHEELOCK OR ALL SYSTEM SENSOR
+ +
SMOKE SMOKE
MUST BE ALL WHEELOCK OR ALL SYSTEM SENSOR
8 ZONE OUTPUT REMOTE RELAY MODULE
+ + + +
SMOKE
GEMC-WL-PIR
HORN
EOLR 2. 2K
GEMC-OUT8
HORN STROBE STROBE HORN HORN HORN STROBE HORN HORN STROBE
EOLR 2. 2K
2-WIRE BURG SLC ADDRESSABLE LOOP
INTERNET REPORTING MODULE
2-WIRE FIRE SLC ADDRESSABLE LOOP
S
+ +
+
S
+
S
SMOKE
+ +
S
SMOKE
+ +
S
SMOKE
+ +
S
SMOKE
GEMC-WL-SMK
8 ZONE OUTPUT REMOTE RELAY MODULE STROBE
EOLR 2. 2K
EOLR 2. 2K
EOLR 2. 2K
EOLR 2. 2K
EOLR 2. 2K
EOLR 2. 2K
}
(11, MAX. )
GEMC-BSLC-1PT
HORN HORN HORN STROBE STROBE
FWC-FSLC-SMK
GEMC-RM3008
OUTPUT MODULE
SMOKE DETECTOR
PIR
GEM-2D
SINGLE POINT CONVENTIONAL ZONE EXPANDER ADDRESSABLE SMOKE DETECTOR STROBE STROBE HORN HORN HORN
8 ZONES OF CONVENTIONAL 2-WIRE SMOKES PULL STATIONS AND/OR HEAT DETECTORS
GEMC-WL-HEAT
SECOND DOOR ACCESS CONTROL ACCESSORY
GEMC-WL-DT
HEAT DETECTOR
(ONE FOR EACH GEM-ACM1D)
GEMC-RM3008 GEMC-BSLC-DT
STROBE STROBE
OUTPUT MODULE
FWC-FSLC-HEAT
STROBE HORN
GEMC-FPRINT
PRINTER MODULE
GEMC-WL-WD2
· 4 ON-BOARD NAC CIRCUITS (CLASS B) (SHOWN) -- or -· 2 ON-BOARD NAC CIRCUITS (CLASS A)
Single Fire initiating N/O device
DUAL TECH PIR
(11, MAX. )
DUAL TECH PIR
GEMC-BSLC Burg SLC Mod. devices, 4 on board NACs, 8 partitions (No Loop Isolator/Extender required) 32 Point GEM-C Commercial Combo. Fire/Burg System Kit Similar to above, but with ·24V Panel, 32 Points via commercial addressable, wireless or conventional fire or burg. devices, 2 on board NACs, 8 partitions (No Loop Isolator/Extender required) ·Locking, Medium Red Enclosure, 16 x 17" door, with 14. 25" x 16" base. [. . . ] Application examples: elevator recall, HVAC shutdown, add'l NAC output with power supply Addressable SLC Fire Pull Station Tool for address-programming SLC devices ** Smoke/Heat 6" Base, required for FWC-FSLC- SMK and HEAT devices 12VDC Power Supply for Fire Bus, remote supervised. Red 14 x 16" can, connects to 120VAC, supports 32Ah standby batts. [. . . ]